Construction
Washable replaceable pleat air filters usually use aluminum alloy or galvanized sheet as the outer frame, with good corrosion resistance and strength. The outer frame is designed to be removable for easy replacement of filter material. The filter material is generally made of green white cotton or polyester fiber and other materials, which not only have a high dust capacity, but also can be cleaned and reused many times
Replacement Cycle
The pressure difference reaches 2 times the initial value
Visible filter material surface dust > 50% area
Typical cycle:
Washable filter material: 2-3 months/time (weekly purge)
Unwashable filter material: 1 month/time
| Technical Specification | ||||||||||
| Filter Type | Pleated Filter | |||||||||
| Filter Class (EN 779) | G4 | |||||||||
| Filter Media & Seperator | Polyester fiber | |||||||||
| Filter Frame | Aluminum/Galvanized | |||||||||
| Temperature Resistance | 80°C | |||||||||
| Max. Temperature | 100°C | |||||||||
| Relative Humidity | 100% | |||||||||
| Rec. Final Pressure Drop | 250 Pa. | |||||||||
FEATURES
▸Removable design for easy installation and maintenance.
APPLICATION
| Dimensions & Technical Details | |||||||
| Bags (Pcs) |
Size (mm) |
Rated Air Flow
(m³/h)
|
I.N.P
(Pa)
|
F.N.P
(Pa)
|
Efficiency | ||
| RT-LGC7725 | 595×595×25 | 1700/3400 | <40/80 | <250 | 95% | ||
| RT-LGC5525 | 495×595×25 | 1200/2400 | <40/80 | <250 | 95% | ||
| RT-LGC1725 | 295×595×25 | 850/1700 | <40/80 | <250 | 95% | ||
| RT-LGC7746 | 595×595×46 | 1700/3400 | <40/80 | <250 | 95% | ||
| RT-LGC5546 | 495×595×46 | 1200/2400 | <40/80 | <250 | 95% | ||
| RT-LGC1746 | 295×595×46 | 850/1700 | <40/80 | <250 | 95% | ||
| RT-LGC7796 | 595×595×96 | 1700/3400 | <40/80 | <250 | 95% | ||
| RT-LGC5596 | 495×595×96 | 1200/2400 | <40/80 | <250 | 95% | ||
| RT-LGC1796 | 295×595×96 | 850/1700 | <40/80 | <250 | 95% | ||
| Note: Other specifications can be customized according to requirements. | |||||||
Replacement cycle standard reference
-
ASHRAE 52.2-2017: It is recommended that the weight increase ≤50% when replacing the filter material
-
EN 779:2012: MPPS efficiency after washing shall not be lower than the lower limit of the original grade
-
GB/T 14295-2019: Metal frame corrosion area > 5% needs to be scrapped