Technical Specification
Filter Type Deep Pleated Filter
Filter Class (EN 1822) E10, E11, E12, H13, H14
Filter Media & Seperator
Microfine Glass Fiber
Frame Material  Stainless Steel / Galvanised 
Sealant Silica Gel
Final Resistance 350Pa (Suggestion)
Temperature Resistance 280 °C
Humidity Resistance (Relative Humidity) 100%RH

Description

Construction

Filter Media:  Employing premium high-temperature resistant glass fiber filter paper
Frame: Constructed from either a durable stainless steel frame or a galvanized steel frame, providing structural integrity and resistance to thermal stress and corrosion.
Sealant: high-temperature resistant silica gel as a sealant. This sealant maintains its elasticity and sealing properties even at elevated temperatures.
Sealing Strip: A specialized high-temperature sealing strip is integrated to guarantee a leak-free installation

Features

▸Large Specific Surface Area  and High Dust Capacity
▸Uniform Fold Distance
▸Stable Air Flow
▸High Filtration Efficiency
▸Excellent Air Tightness
▸Low energy consumption

Product Usage

High temperature resistant and high-efficiency filters are designed with baffles. Corrugated baffles can accurately maintain the fold spacing and maximize the use of filter material with minimal resistance. It is widely used in pharmaceutical, food processing, electronic manufacturing, semiconductor, laboratory clean room, and high temperature baking equipment and other fields. It is mainly used in the end filtration system to ensure that the air cleanliness meets the strict requirements
Technical Specification
Filter Type Deep Pleated Filter
Filter Class (EN 1822) E10, E11, E12, H13, H14
Filter Media & Seperator
Microfine Glass Fiber
Frame Material  Stainless Steel / Galvanised 
Sealant Silica Gel
Final Resistance 350Pa (Suggestion)
Temperature Resistance 280 °C
Humidity Resistance (Relative Humidity) 100%RH
Curve of Air Flow and Resistance
Dimensions & Technical Details
Depth
(mm)
 Size
(mm)
Rated Airflow
(m³/h)
Filter Area
(m²)
Initial Resistance(Pa)
E10 E11 E12 H13 H14
Box Type 150mm Depth
150 305×610 500/700 4.25 <100/130 <120/150 <140/170 <180/220 <200/240
610×610 1000/1500 7.97
1220×610 2000/2800 15.68
1220×915 2800/3800 23.60
Box Type 220mm Depth
220 305×610 800/1000 6.76 <100/130 <120/150 <140/170 <180/220 <200/240
610×610 1500/2100 12.68
1220×610 2800/4000 24.95
1220×915 3800/5400 37.54
Box Type 292mm Depth
292 305×610 900/1300 9.55 <100/130 <120/150 <140/170 <180/220 <200/240
610×610 1800/2600 17.90
1220×610 3400/4800 35.21
1220×915 4200/6800 52.99
Note: other specifications can be customized according to requirements
Filter Grades Available
Grade Efficiency @MPPS* Application
E10 >85% For The Removal of Smoke or Very Low Grade Cleanroom Applications
E11 >95% Start of HEPA Range – Not Available
E12 >99.5% Lower Grade Cleanrooms
H13 >99.95% Cleanrooms And Industrial Applications
H14 >99.995% Higher Grade  Cleanrooms And Industrial Applications
U15 >99.9995% Not often Requested Due to High Resistance / Energy Consumption
U16 >99.9997%